Proudly Designed, Developed & Manufactured in Cleveland, Ohio, USA 🇺🇸(216) 663-8830info@humongousfan.comM-F, 8 AM - 6 PMInternational Orders
Humongous Fan
Request a Quote Call (216) 663-8830
(216) 663-8830info@humongousfan.comMon to Fri, 8AM to 6PM EST · 23103 Miles Rd, Cleveland, OH 44128

HF1600 16 Foot 8 Blade HVLS Fan

Energy savings estimate

16 ft HF Series HVLS fan for large bay warehouses and tall ceilings.

Request a Quote
SKU:
HF-1600
Category:
Share
HF160016 FT

HF1600 16 foot HVLS fan

HF1600 view 1HF1600 view 2HF1600 view 3HF1600 view 4
SpecificationsElectricalMountingDownloads
Diameter16 ft
Airflow at max RPM92,298 CFM
Blades8 × Performance Engineered™
Max speed44 RPM
Motor0.5 HP gearmotor
Direct breeze region56–64 ft diameter
Sound level<57 dBA
Minimum airfoil clearanceSides 2 ft · Ceiling 3–4 ft
Fan weight140 lb
Electrical frequency60 Hz
Maximum full load amps208–240V 3φ 1.90 A · 460–480V 3φ 0.95 A
Motor enclosureTotally enclosed, fan cooled
ControllerNEMA 1 VFD with disconnect
Standard mountI-beam, Z-purlin or open joist
Mount extensions1, 2, 3 and 6 ft
Warranty5 years, all parts

Energy savings estimate

What one HF1600 pays back

Destratification in the heating season and a thermostat offset in the cooling season is where the money comes from. Put your own square footage, ceiling height and utility rate in and the calculator returns the number for your building.

Run the numbers

Airflow92,298
Power draw0.5 HP
Max speed44 RPM
Warranty5 yr, all parts

The HF1600 is a 16 foot HVLS fan built for high bay warehouses, distribution centers and manufacturing floors. Its eight Performance Engineered Blades move 92,298 CFM at 44 RPM, and at half speed on a clear floor the direct breeze reaches across a circle 56 to 64 feet wide.

Sizing and placement

Size the fan to the part of the building where people work. A work area around 60 feet across is a good match for one HF1600 set over its center. For a larger floor, add fans at least 40 feet apart, center to center, which is 2.5 times the diameter.

The blades need to sit at least 10 feet above the floor, 3 to 4 feet below the ceiling deck and 2 feet away from any obstruction at the sides, so a 13 to 14 foot ceiling is the practical minimum. Mount it clear of lights, sprinklers, overhead piping, HVAC equipment, crane systems and conduit. On a sloped beam, the beam mount adjusts up to 30 degrees and keeps the fan vertical, and 1, 2, 3 and 6 foot extensions bring it down under a tall roof.

What ships with it

It runs on a 0.5 HP totally enclosed, fan cooled gearmotor and takes 110 to 120 V single phase, 208 to 240 V single or three phase, or 460 to 480 V three phase service. Whatever comes in, the VFD sends three phase power to the motor. Every HF1600 comes with a NEMA 1 wall mounted VFD with safety disconnect, on and off toggle, speed dial and integrated sprinkler shut off, along with the safety cable, hub clips and hub retainer. The fan weighs 140 lb and stays below 57 dBA under the fan at three quarter speed.

In summer the breeze can make a hot floor feel up to 10°F cooler. In heating season, running at 5 to 15 percent speed moves warm air off the ceiling and back down to the floor. It is built in Cleveland with a five year warranty on all parts.

Privacy Settings
We use cookies to enhance your experience while using our website. If you are using our Services via a browser you can restrict, block or remove cookies through your web browser settings. We also use content and scripts from third parties that may use tracking technologies. You can selectively provide your consent below to allow such third party embeds. For complete information about the cookies we use, data we collect and how we process them, please check our Privacy Policy
Youtube
Consent to display content from - Youtube
Vimeo
Consent to display content from - Vimeo
Google Maps
Consent to display content from - Google
Spotify
Consent to display content from - Spotify
Sound Cloud
Consent to display content from - Sound
Int'l Orders
Cart Overview