An HVLS fan is a large piece of equipment hanging over people, vehicles and inventory, so HVLS fan safety gets questions from everyone involved in a project: the facility manager, the fire marshal, the sprinkler contractor, the insurance carrier and the electrician. This is what comes on every Humongous Fan, how it is meant to be installed, and what to have ready when someone asks.

The safety hardware on every fan
Every HF Series and Essential 6 fan carries the same set of safety features:
- Safety cable
- Hub clips
- Hub retainer
- Dual method fastening of all joined components
- Integrated sprinkler shut-off
None of these are options or add-ons. They come standard at every size, from the 8 foot HF800 to the 24 foot models.
Sprinklers and fire protection
Fire protection is the question that comes up most often during plan review. Each Humongous Fan has an integrated sprinkler shut-off. Fire code requirements for fans in a sprinklered building vary by jurisdiction, and how the shut-off ties into the building depends on how the fire alarm and sprinkler systems are designed. Bring the sprinkler designer and the fire marshal into the conversation before the fans are installed.
Placement matters too. Mount fans away from sprinkler heads and sprinkler piping, along with light fixtures, other overhead piping, HVAC equipment, crane systems, conduit and wiring. Planning the fan locations on the same drawing as the sprinkler layout avoids most of the problems before anything is hung.
Height and clearances
The blades of a Humongous Fan must be at least 10 feet above the floor, as OSHA requires. In buildings with forklifts, lifts, cranes or tall vehicles, the fan has to be higher than whatever moves underneath it.
Every fan needs 2 feet of clearance at the sides. Clearance above the fan depends on its size:
| Fan size | Minimum clearance to the ceiling |
|---|---|
| 8, 10, 12 and 16 ft | 3 to 4 ft |
| 20 ft | 4 to 6 ft |
| 24 ft | 6 to 8 ft |
When a building has more than one fan, keep them no less than two and a half times the fan diameter apart.
Mounting to the structure
Standard mounts cover I-beam, Z-purlin and open joist structures. Mounting extensions come in 1, 2, 3 and 6 foot lengths, and for beam mounts an extension kit is normally needed. The 0.5 HP fans use a short mount and the 1.5 and 3 HP fans use a long mount. Kits are standard and modifications are made to order, so an unusual roof structure should be reviewed before the order goes in.

The structure itself has to carry the fan. Weights run from 95 lbs for the E6 10 Ft to 262 lbs for the HF24. Our structural mounting guide explains what an engineer will want to see.
Electrical safety at the controller
Each HF Series fan comes with a NEMA 1 wall mounted VFD with a safety disconnect, an on/off toggle and a speed pot. The Essential 6 runs on a VFD with speed set from the keypad. Regardless of whether the building feeds the controller single phase or three phase power, the power to the fan motor is always three phase. Supply wiring to the VFD must be 14 AWG or larger.
Electrical frequency is 60 Hz for 0.5 HP models, 55 Hz for 20 ft models and 50 Hz for 24 ft models. Follow the applicable installation instructions. The available Essential 6 manual covers 10 to 20 ft; request E6 24 installation and controller-setting instructions directly from Humongous Fan.
Indoor fans, outdoor installs
Humongous Fan fans are designed for indoor use. A fan installed outdoors or under a canopy follows the supplementary tethering guide, and the Blade Tip Tethering System is available as an optional purchase when an installation needs it.
Keeping it safe after installation
The gear motor is totally enclosed, fan cooled and lubricated for life. During routine maintenance, check the safety cable, the hub clips and retainer, and the fasteners, and look for any sign of an oil leak at the motor. Our maintenance guide walks through the inspection. The warranty is 5 years on all parts.
What to bring to plan review
When the fire marshal, insurance carrier or building owner asks about the fans, it helps to have the cut sheet for each model, the installation manual, the mounting details for the structure, and the fan locations drawn against the sprinkler and lighting layouts. You can download the cut sheet anytime, and our team can help with the rest.
Humongous Fan designs and builds its fans in Cleveland, Ohio. Read about HVLS fan installation or send us your building drawings and we will help plan the fan locations.